Solar Field Parameters
Option 1 and Option 2
For Option 1 (solar multiple mode), Solar Advisor calculates the total required aperture and number of loops based on the value you enter for the solar multiple. For option 2 (field aperture mode), Solar Advisor calculates the solar multiple based on the field aperture value you enter. Note that Solar Advisor does not use the value that appears dimmed for the inactive option.
Solar multiple
The field aperture expressed as a multiple of the aperture required to operate the power cycle at its design capacity.
Field aperture
The total solar energy collection area of the solar field in square meters. Note that this is less than the total mirror surface area.
Row spacing (m)
The centerline-to-centerline distance in meters between rows of collectors, assuming that rows are laid out uniformly throughout the solar field.
Stow angle (degrees)
The collector angle during the hour of stow. A stow angle of zero for a northern latitude is vertical facing east, and 180 degrees is vertical facing west.
Deploy angle (degrees)
The collector angle during the hour of deployment. A deploy angle of zero for a northern latitude is vertical facing due east. Default is 10 degrees.
Solar Field
Describes how collectors and header pipes are laid out in the solar field. See Solar Field "H" and "I" Layout Options for details.
Header pipe roughness (m)
The header pipe roughness is a measure of the internal surface roughness of the header and runner piping. Solar Advisor uses this value in calculation of the shear force and piping pressure drop in the headers.
HTF pump efficiency
The electrical-to-mechanical energy conversion efficiency of the field heat transfer fluid pump. This value accounts for all mechanical, thermodynamic, and electrical efficiency losses.
Freeze protection temp (ºC)
The temperature at which freeze protection equipment is activated. The fluid temperature is maintained at this value during hours that freeze protection is operating.
Irradiation at design (W/m2)
The design point direct normal radiation value, used in solar multiple mode to calculate the aperture area required to drive the power cycle at its design capacity. Also used to calculate the design mass flow rate of the heat transfer fluid for header pipe sizing. See Choosing a Design Irradiation Value for details.
Allow partial defocusing
Partial defocusing assumes that the tracking control system can adjust the collector angle in response to the capacity of the power cycle (and thermal storage system, if applicable). See Defining Collector Defocusing for details.
Heat Transfer Fluid
Field HTF fluid
The heat transfer fluid (HTF) used in the heat collection elements and headers of the solar field. Solar Advisor includes the following options in the HTF library: Solar salt, Caloria, Hitec XL, Therminol VP-1, Hitec salt, Dowtherm Q, Dowtherm RP. You can also define your own HTF using the user-defined HTF fluid option
User-defined HTF fluid
To define your own HTF, choose User-defined for the Field HTF fluid and specify a table of material properties for use in the solar field. You must specify at least two data points for each property: temperature, specific heat, density, viscosity, and conductivity. See Specifying a Custom Heat Transfer Fluid for details.
Design loop inlet temp (ºC)
The temperature of HTF at the loop inlet under design conditions. The actual temperature during operation may differ from this value. Solar Advisor sets the power cycle's design outlet temperature equal to this value.
Design loop outlet temp (ºC)
The temperature of the HTF at the outlet of the loop under design conditions. During operation, the actual value may differ from this set point. This value represents the target temperature for control of the HTF flow through the solar field and will be maintained when possible.
Min single loop flow rate (kg/s)
The minimum allowable flow rate through a single loop in the field.
Max single loop flow rate (kg/s)
The maximum allowable flow rate through a single loop in the field.
Header design min flow velocity (m/s)
A calculated value that indicates the minimum flow velocity in the field corresponding to the specified minimum single loop flow rate. This value is calculated using the density of the HTF at the design inlet temperature and the maximum specified receiver diameter.
Header design max flow velocity (m/s)
A calculated value that indicates the maximum flow velocity in the field corresponding to the specified maximum single loop flow rate. This value is calculated using the density of the HTF at the design outlet temperature and the minimum specified receiver diameter.
Initial field temperature (ºC)
Temperature of the HTF in the solar field in the first time step of the simulation (Hour one, typically the hour beginning at midnight on January 1). The value affects the system's performance in the first hours of the simulation, but typically has little impact on subsequent hours and total annual plant performance.
Design Point
Single loop aperture (m2)
The aperture area of a single loop of collectors, equal to the product of aperture width, reflective area, times the structure length times the number of collector assemblies per loop according to the distribution of the up to four collector types in the field. This area does not include non-reflective surface on the collector or non-reflective space between collectors.
Loop optical efficiency
The optical efficiency when incident radiation is normal to the aperture plane, not including end losses or cosine losses. This value does not include thermal losses from piping and the receivers.
Total loop conversion efficiency
The total conversion efficiency of the loop, including optical losses and estimated thermal losses. Used to calculate the required aperture area of the solar field.
Total required aperture, SM=1 (m2)
The exact mirror aperture area required to meet the design thermal output for a solar multiple of 1.0. Solar Advisor uses the required aperture to calculate the actual aperture. The actual aperture may be slightly more or less than the required aperture, depending on the collector dimensions you specify on the Collectors page.
Required number of loops, SM=1
The exact number of loops required to produce the total required aperture at a solar multiple of 1.0. This number may be a non-integer value, Solar Advisor rounds this value to the nearest integer to caculate the value of the actual number of loops variable.
Actual number of loops
The actual number of loops in the field, equal to the solar multiple times the required number of loops at a solar multiple of 1.0. The required number of loops is rounded to the nearest integer to represent a realistic field layout.
Actual aperture (m2)
The actual aperture area based on the actual number of loops in the field, equal to the single loop aperture times the actual number of loops.
Actual solar multiple
For Option 1 (solar multiple mode), the calculated solar multiple based on the actual (rounded) number of loops in the field. For Option 2 (field aperture mode), the solar multiple value corresponding to the thermal output of the field based at design point: The actual aperture divided by the field thermal output.
Field thermal output (MWt)
The thermal energy delivered by the solar field under design conditions at the actual solar multiple.
Collector Orientation
Collector tilt (degrees)
The angle of all collectors in the field in degrees from horizontal, where zero degrees is horizontal. A positive value tilts up the end of the array closest to the equator (the array's south end in the northern hemisphere), a negative value tilts down the southern end. Solar Advisor assumes that the collectors are fixed at the tilt angle.
Collector azimuth (degrees)
The azimuth angle of all collectors in the field, where zero degrees is pointing toward the equator, equivalent to a north-south axis. Solar Advisor assumes that the collectors are oriented 90 degrees east of the azimuth angle in the morning and track the daily movement of the sun from east to west.
Mirror Washing
Solar Advisor reports the water usage of the system in the results based on the mirror washing variables. The annual water usage is the product of the water usage per wash and 365 (days per year) divided by the washing frequency.
Water usage per wash
The volume of water in liters per square meter of solar field aperture area required for periodic mirror washing.
Washing frequency
The number of days between washing.
Single Loop Configuration
Number of SCA/HCE assemblies per loop
The number of individual solar collector assemblies (SCAs) in a single loop of the field. Computationally, this corresponds to the number of simulation nodes in the loop. See Specifying the Loop Configuration for details.
Edit SCAs
Click Edit SCAs to assign an SCA type number (1-4) to each of the collectors in the loop. Use your mouse to select collectors, and type a number on your keyboard to assign a type number to the selected collectors. Solar Advisor indicates the SCA type by coloring the rectangle representing the collector in the diagram, and displaying the type number after the word "SCA." See Specifying the Loop Configuration for details.
Edit HCEs
Click Edit HCEs to assign a receiver type number (1-4) to each of the collectors in the loop. Use your mouse to select collectors, and type a number on your keyboard to assign a type number. Solar Advisor indicates the HCE type by coloring the line representing the receiver, and displaying the type number after the word "HCE." See Specifying the Loop Configuration for details.
Edit Defocus Order
Click Edit Defocus Order to manually define the defocus order of the collectors in the field. Click an assembly to assign the defocus order. You should assign each collector a unique defocus order number. See Defining Collector Defocusing for details.
Reset Defocus
Click to reset the defocus order to the default values, starting at the hot end of the loop and proceeding sequentially toward the cold end of the loop. See Defining Collector Defocusing for details.
|